Water-Source Heat Pump Not Cooling: Facilities Troubleshooting Checklist
For a water-source heat pump that runs but does not cool, verify thermostat demand, airflow, filter condition, loop-water availability, condensate safeties, and whether neighboring units are affected. Refrigerant and internal electrical diagnosis should be escalated.
Last reviewed 2026-09-12 · General facility-maintenance information, not a substitute for site procedures, manufacturer instructions, codes, or qualified professional judgment.
Safety boundary
Symptom → cause → first move
Fan runs, air not cool
Check: Compressor/refrigerant/loop/control issue
First move: Check loop pattern and alarms.
One unit hot
Check: Local issue
First move: Check airflow, controls, safeties.
Many units hot
Check: Loop plant/control issue
First move: Check shared system.
Repeated lockout
Check: Safety/equipment fault
First move: Record code before reset.
Weak airflow
Check: Filter/fan/coil issue
First move: Correct basic airflow.
What to check first
Bring these
- Thermometer
- Flashlight
- Replacement filter
- Camera/phone
- BAS access if authorized
Before touching anything
- Confirm the exact location and complaint.
- Photograph labels, settings, and error codes before changing anything.
- Know how to isolate water, power, or the affected area if needed.
- Follow site-specific PPE, lockout/tagout, ladder, roof, and access procedures.
Step-by-step procedure
- 1Verify cooling callRecord room temp, setpoint, mode, schedule.
- 2Check airflowInspect filter, return, supply, and fan.
- 3Look for condensate troubleCheck pan, float switch, and pump.
- 4Check operator-visible loop dataUse BAS/gauges if intended for operator use.
- 5Compare nearby unitsMany affected units point to shared loop conditions.
- 6Record lockout/LED codeTake a photo before clearing anything.
- 7Escalate sealed-system/electrical workCompressor, refrigerant, and energized testing require qualified service.
Stop and call a licensed professional when
- Refrigerant diagnosis is required
- Electrical panel work is required
- Repeated high/low pressure lockouts
- Loop water unavailable building-wide
- Water leak inside cabinet
Common mistakes
- Condemning compressor too early
- Resetting before recording codes
- Treating shared loop issue as many local failures
- Opening water/refrigerant circuits
- Ignoring airflow
FAQ
How is WSHP different from split system?
It exchanges heat with a building water loop rather than its own outdoor condenser.
Can one loop problem affect many units?
Yes; shared loop conditions can affect many heat pumps.
Should I reset lockout?
Record the code first and follow site procedure.
Can dirty filter stop cooling?
Yes; airflow problems reduce capacity and can trigger safeties.