No Cooling: Full Troubleshooting Guide

A space is not holding temperature and occupants are complaining. Work from the thermostat outward through power, airflow, and condensate before assuming the equipment failed.

Last reviewed 2026-09-12 · General facility-maintenance information, not a substitute for site procedures, manufacturer instructions, codes, or qualified professional judgment.

Most common callRoutine + escalationLast reviewed 2026-09-12
Ask AI About This

Quick answer

Confirm the call for cooling at the thermostat, confirm the unit has power and is not locked out on a safety, then check the two things that cause most no-cooling calls: a loaded filter and a plugged condensate drain with a tripped float switch. Anything involving refrigerant, energized troubleshooting, or gas requires a licensed technician.

Safety boundary

Do not open energized electrical compartments, jumper safeties, bypass a float switch, add or recover refrigerant, or repeatedly reset a tripped breaker. Refrigerant work requires EPA Section 608 certification. If you smell gas, see smoke, hear arcing, or see scorched wiring, leave the equipment off and call qualified personnel immediately.

Likely causes

  • Thermostat is in the wrong mode, set above space temperature, or on an unoccupied schedule
  • Dirty or collapsed air filter starving airflow
  • Plugged condensate drain and a tripped float switch (safety shut the unit down on purpose)
  • Tripped breaker, blown control fuse, or a disconnect left open after other work
  • Closed dampers, blocked return, or closed supply diffusers in the affected area
  • Frozen evaporator coil from low airflow
  • Dirty condenser coil or blocked outdoor airflow raising head pressure
  • Contactor, capacitor, or control-board failure (qualified technician)
  • Low refrigerant charge or a leak (licensed technician only)
  • Compressor or reversing-valve failure (licensed technician only)

Symptom → cause → first move

Fan runs, air is not cold

Check: Supply vs return air temperature split and whether the outdoor unit is running

First move: Check filter and condenser airflow, then hand off for refrigerant and electrical diagnosis

Nothing runs at all

Check: Thermostat display, breaker position, unit disconnect, and float switch

First move: Restore an intentionally opened disconnect only if you know why it was opened; otherwise document and escalate

Unit runs then shuts off quickly

Check: Filter loading, iced coil, and whether the space is short cycling on a safety

First move: Replace filter, let a frozen coil thaw with fan only, then reassess

Water present near the unit

Check: Condensate pan, drain line, and float switch

First move: Clear the drain if it is accessible and dry the area; escalate if water is near electrical equipment

What to check first

Bring these

  • Flashlight or headlamp
  • Correct-size replacement filters
  • Pocket thermometer or infrared thermometer
  • Wet/dry vacuum for accessible condensate drains
  • Nitrile gloves, safety glasses, and hearing protection on a roof

Before touching anything

  • Immediate safety check: look for smoke, burning smell, sparking, standing water near electrical equipment, or an audible refrigerant leak. Any of those means stop and call qualified help.
  • Confirm you are authorized to be on the roof or in the mechanical room, and follow your site's lockout/tagout procedure
  • Ask what changed: recent power loss, filter change, tenant work, or a thermostat adjustment
  • Note the space temperature, setpoint, and time the complaint started

Step-by-step procedure

  1. 1Verify the complaint at the thermostatRead the space temperature and setpoint. Confirm mode is Cool, the fan setting is correct, and the schedule is not in unoccupied setback. A blank display points to power or a tripped safety upstream.
  2. 2Confirm airflow at the diffusersFeel for air movement in the affected space. No airflow anywhere is a fan or power problem; airflow in one area only is a damper, balancing, or blocked-return problem.
  3. 3Inspect the filterPull the filter and hold it to the light. If it is loaded, replace it with the same size and rating, note the date, and reassess after 20 minutes of runtime.
  4. 4Check the condensate drain and float switchLook for water in the pan or a wet trap. Clear an accessible drain with a wet/dry vacuum. If the float switch tripped, the unit shut itself down for a reason: clear the cause, never bypass the switch.
  5. 5Look at the evaporator coil for iceIce means restricted airflow or a refrigerant issue. Switch to fan-only to thaw, correct filters and airflow, and if ice returns, escalate for refrigerant diagnosis.
  6. 6Check the condenser and outdoor airflowClear leaves, debris, and stored material from around the unit. Note any heavy coil fouling for a cleaning work order. Do not remove electrical panels.
  7. 7Confirm power state and documentNote breaker and disconnect positions without opening panels. Record model, serial, error codes on the display, and what you already checked, then escalate if the space still is not cooling.

Routine fixes that make sense here

  • Replace a loaded filter with the correct size and rating
  • Clear an accessible condensate drain and pan, then flush
  • Reset a float switch after the water cause is corrected
  • Reopen supply diffusers and clear blocked returns
  • Remove debris from the outdoor unit and clear the service clearance
  • Correct thermostat schedule, mode, and setpoint

What this guide will not tell you

One symptom does not prove one cause. Treat everything here as a narrowing process, not a diagnosis, and confirm with readings and equipment documentation before replacing parts.

Preventive maintenance

  • Set a filter-change interval by equipment and season and track it (see the Toolbox filter-change calculator)
  • Flush condensate drains and treat pans before and during cooling season
  • Clean condenser coils annually and keep three feet of clearance
  • Log supply and return temperatures monthly to catch drift early
  • Verify thermostat schedules after every power outage or tenant change
  • Book a pre-summer HVAC inspection before the first hot week

Stop and call a licensed professional when

  • Burning smell, smoke, sparking, arcing sounds, or scorched wire insulation
  • A breaker that trips again after one reset
  • Any need to open an energized electrical compartment or take live readings
  • Suspected refrigerant leak, oily residue at fittings, or hissing at the coil
  • Gas odor, suspected carbon monoxide, or combustion equipment concerns
  • Standing water near electrical equipment or a panel
  • Rooftop access without required fall protection or authorization
  • Repeated ice-up after airflow is corrected

Common mistakes

  • Bypassing a float switch to get the unit running again
  • Resetting a breaker repeatedly instead of finding the fault
  • Installing the wrong filter size and leaving bypass gaps
  • Assuming low refrigerant before checking airflow
  • Closing the call without documenting model, serial, and readings

FAQ

How long should I wait after a filter change before rechecking?

Give the unit at least 20 minutes of runtime, then compare supply and return air temperatures again.

The breaker is off. Can I just turn it on?

Only if you know why it is off and nobody is working on the equipment. If it trips again, stop and call a licensed electrician or HVAC technician.

Can I add refrigerant if it seems low?

No. Refrigerant handling requires EPA Section 608 certification and proper recovery equipment.