Water Leak: Find the Source and Control the Damage
Water shows up where it does not belong. Protect people and equipment first, then trace the water path upward and uphill before you decide what failed.
Last reviewed 2026-09-12 · General facility-maintenance information, not a substitute for site procedures, manufacturer instructions, codes, or qualified professional judgment.
Quick answer
Safety boundary
Likely causes
- HVAC condensate: plugged drain, cracked pan, failed pump, or sweating uninsulated pipe
- Roof leak entering at a penetration, seam, or clogged roof drain during rain
- Domestic supply leak at a fitting, valve, flex connector, or fixture stop
- Drain or waste leak that only shows when the fixture above is used
- Fixture overflow or a failed flushometer or fill valve
- Water heater tank, relief valve, or connection leak
- Sprinkler or fire-protection piping (life safety: qualified contractor only)
- Groundwater or surface water intrusion at grade or below grade
- Failed exterior sealant, window, or door threshold
Symptom → cause → first move
Only leaks when it rains
Check: Roof drains, penetrations, parapet, and window heads above the wet area
First move: Contain the water, photograph the pattern, and schedule a roofing contractor
Leaks in cooling weather, dry when the unit is off
Check: Condensate pan, drain trap, pump, and pipe insulation
First move: Clear the accessible drain and confirm the float switch works
Constant drip regardless of weather or equipment
Check: Supply piping, valves, and fixture connections above the wet area
First move: Isolate at the nearest accessible valve and call a plumber for repair
Only leaks when a fixture is used
Check: Drain, trap, and closet flange of the fixture above
First move: Take the fixture out of service and repair or escalate
What to check first
Bring these
- Wet/dry vacuum, mop, and absorbent material
- Buckets, plastic sheeting, and caution signs or cones
- Flashlight, moisture meter if available, and a camera
- Nitrile gloves and safety glasses
- Ladder rated for the work and a second person for the area below
Before touching anything
- Immediate safety check: is water near electrical equipment, lighting, or a panel? Is a ceiling sagging? Is the water clean, gray, or sewage? Any of those changes the response.
- Barricade the area and protect equipment, records, and inventory
- Locate the nearest accessible isolation valve before you open anything
- Note the time, weather, and whether HVAC is running
Step-by-step procedure
- 1Make the area safeKeep people out, de-energize affected lighting or equipment through the proper procedure, and place containment. If electricity may be involved, stop and call an electrician.
- 2Stop the source if you can do it safelyClose the fixture stop or the accessible branch valve. Do not shut a main or a fire-protection valve without authorization and notification.
- 3Map the wet areaMark the extent of the water on the floor or ceiling and photograph it. Water travels along joists, conduit, and decking, so the origin is often uphill of the drip.
- 4Test the weather-versus-equipment questionIf it only leaks during rain, treat it as building envelope. If it leaks whenever HVAC runs, treat it as condensate. If it is constant, treat it as pressurized supply piping.
- 5Open the space above only when it is safeRemove a ceiling tile at the edge of the wet area with the area cleared below. Look for staining direction, rust trails, and dripping fittings.
- 6Perform the routine fix or escalateClear condensate drains, tighten an accessible drain slip nut, or replace a supply-side component only if it is your authorized work. Anything pressurized, structural, or life-safety goes to a licensed trade.
- 7Dry, document, and follow upExtract water, run air movers, and record what you found. Log ceiling and drywall damage for repair and reinspect in 24 hours for recurrence and mold risk.
Routine fixes that make sense here
- Clear an accessible condensate drain, pan, and trap
- Replace a failed condensate pump on non-regulated equipment
- Insulate a sweating cold-water or condensate line
- Tighten or reseal an accessible P-trap slip joint
- Clear a clogged roof drain strainer from a safe, authorized position
- Replace a failed flushometer or fill-valve component
Document like it will be a claim
Preventive maintenance
- Walk roof drains and gutters quarterly and after every major storm
- Flush and treat condensate drains before cooling season
- Insulate cold piping in humid areas to prevent condensation drips
- Inspect exterior sealant, thresholds, and window perimeters annually
- Test float switches and condensate pumps during PM visits
- Keep an extraction kit and containment supplies staged onsite
Stop and call a licensed professional when
- Water contacting or entering electrical equipment, panels, or fixtures
- Sagging ceiling, bowed drywall, or any structural concern
- Sewage, gray water, or a suspected backflow event
- Fire-sprinkler piping, heads, or fire-pump equipment
- Continuing pressurized leak that you cannot isolate
- Suspected asbestos-containing material or damaged insulation
- Roof work needing fall protection or a roofing warranty holder
- Water reaching an elevator pit or machine room
Common mistakes
- Replacing ceiling tile before the source is confirmed
- Assuming a roof leak during dry weather
- Working in standing water near powered equipment
- Shutting a fire-protection valve without authorization
- Skipping documentation the insurer or contractor will need
FAQ
How do I tell a roof leak from a condensate leak?
Correlate with conditions. Rain-only points to the envelope, cooling-only points to condensate, and a constant drip points to pressurized piping.
Should I cut open drywall to look?
Only if that is your authorized scope and you have confirmed there is no asbestos, no live wiring, and no structural role for that area.